One credit - View out

BREEAM·clause Hea 01.5·p.90

The requirement

BREEAM International New Construction Technical Manual clause Hea 01.5 — words not shown. Read it at the source. The publisher reserves the right to its wording and sells access to it. The clause is held and cited here, and its words are read at the source.

The clause is held and verified. Only its words are withheld.

Read it at the source

What the product must meet

The document’s own listing

Table 13: Window or opening size required as a percentage of surrounding wall area depending on the distance of the desk or workspace to the window or opening lance from of surrounding wall ar metres) X<8 20% 8<X<tl 25% W<X<14 30% X>14 35%

The document’s own compact listing of the limits, as harvested.

Applies to
(all buildings)

How it is proven

Who checks it
Independent body verifies — a certifier, auditor or verifier with no stake

How Klar Cite classifies it

Klar Cite’s reading of the clause, not the scheme’s own claim.

What it asks
Meet — a limit, condition or outcome the product must satisfy
Standing
Required — must be met for the credential
Refers to
Table 13 — places elsewhere in the document

Cite this clause

BREEAM · BREEAM International New Construction Technical Manual · version v7.1 · clause Hea 01.5 · page 90 · build 2026-10-05-0439 · https://klarcite.com/r/2abb6c9c73e3d358

Source document

Record details

Page 90, HEA 01 NATURAL LIGHT. Read in build 2026-10-05-0439, harvested 2026-10-05.

uid 2abb6c9c73e3d358 · document e3e19e8b697bf44b · fidelity verbatim · published 2024